The grease interceptor sizing calculator gives the liquid capacity of a grease interceptor with the meal count method, from the meals in the peak hour, the waste flow, the retention time and the hours of operation.
How the calculation works
- Enter the meals served in the peak hour.
- Choose the waste flow per meal, the retention time and the storage factor for the hours of operation.
- The calculator gives the peak flow, the liquid capacity of the grease interceptor and the size to specify.
Example
A restaurant with a dishwasher serves 80 meals in the peak hour, with 6 gal of waste per meal, a retention time of 2.5 h and 8 hours of operation (storage factor 1). The peak flow is 80 × 6 / 60 = 8.0 gpm. The liquid capacity is 80 × 6 × 2.5 × 1 = 1,200 gal, so the interceptor to specify is 1,250 gal.
Why it matters
The calculator helps plumbers, restaurant designers, kitchen consultants and owners to size a grease interceptor at the planning stage, and to see how a dishwasher, a longer service day or more meals change the size of the tank.
Good to know
Count the meals served in the busiest hour of the busiest day, not the average, and use the waste flow that matches the kitchen equipment. Use the retention time and storage factor of your code. Round the result up to the next size available from the manufacturers, and check that the tank fits in the location, since a large interceptor is often outside and needs excavation, access covers and a place for the pumping truck. A kitchen with a food waste disposer, a pot sink and a dishwasher produces more grease, so choose the safer value if you are in doubt.