Grease interceptor sizing calculator (meal count method)

Enter the meals in the peak hour, the waste flow per meal, the retention time and the hours of operation to get the peak flow and the liquid capacity of a grease interceptor.

Updated on
Your inputs

Value out of range

Results

Liquid capacity of the interceptor

1,200 gal

Peak waste flow
8.0 gpm
Size to specify, in steps of 250 gal
1,250 gal

The grease interceptor sizing calculator gives the liquid capacity of a grease interceptor with the meal count method, from the meals in the peak hour, the waste flow, the retention time and the hours of operation.

How the calculation works

  • Enter the meals served in the peak hour.
  • Choose the waste flow per meal, the retention time and the storage factor for the hours of operation.
  • The calculator gives the peak flow, the liquid capacity of the grease interceptor and the size to specify.

Example

A restaurant with a dishwasher serves 80 meals in the peak hour, with 6 gal of waste per meal, a retention time of 2.5 h and 8 hours of operation (storage factor 1). The peak flow is 80 × 6 / 60 = 8.0 gpm. The liquid capacity is 80 × 6 × 2.5 × 1 = 1,200 gal, so the interceptor to specify is 1,250 gal.

Why it matters

The calculator helps plumbers, restaurant designers, kitchen consultants and owners to size a grease interceptor at the planning stage, and to see how a dishwasher, a longer service day or more meals change the size of the tank.

Good to know

Count the meals served in the busiest hour of the busiest day, not the average, and use the waste flow that matches the kitchen equipment. Use the retention time and storage factor of your code. Round the result up to the next size available from the manufacturers, and check that the tank fits in the location, since a large interceptor is often outside and needs excavation, access covers and a place for the pumping truck. A kitchen with a food waste disposer, a pot sink and a dishwasher produces more grease, so choose the safer value if you are in doubt.

The sprinkler system demand calculator sizes a sprinkler system, the pipe insulation condensation calculator checks cold pipes, the kitchen hood exhaust calculator sizes the exhaust of the cooking line and the hydronic expansion tank calculator sizes a heating system tank.

Frequently asked questions

What does a grease interceptor do?

A grease interceptor is a large tank on the drain line of a commercial kitchen. The wastewater slows down in the tank, so fats, oils and grease float to the surface and stay there, and the cooler water leaves from the bottom. It keeps grease out of the sewer, where it hardens and blocks the pipes.

What is the meal count method?

In this method from the plumbing codes, the liquid capacity is the number of meals served in the peak hour, times the waste flow per meal, times the retention time, times a storage factor that depends on the hours of operation. The result is the volume that the tank needs to hold during the retention time and the hours of service.

What values should I use?

The values in the lists are typical figures from the Uniform Plumbing Code appendix: 6 gallons per meal with a dishwasher and 5 without, a retention time of 2.5 hours for a kitchen with a dishwasher, and a storage factor of 1 for 8 hours up to 3 for 24 hours. The code in your jurisdiction may be different, and some require a minimum size.

What does the calculator leave out?

The calculator leaves out the fixture-flow method, the size of the inlet pipe, the venting and the cleaning schedule, the minimum depth of the tank and the needs of the sewer utility. Some jurisdictions use the sum of the flow rates of the fixtures instead. Ask the plumbing inspector which method is required, and size the tank for it.