Steam trap sizing calculator: how much condensate a trap must discharge

Enter the heat load, the steam pressure, the back pressure and the safety factor to get the condensate load, the capacity of the steam trap required, the capacity per trap and the differential pressure.

Updated on
Your inputs
Btu/h

Value out of range

psig

Value out of range

Value out of range

Results

Condensate load

681.0 lb/h

Required trap capacity (with safety factor)
2,043.1 lb/h
Capacity needed per trap
1,021.6 lb/h
Differential pressure across the trap
90 psi
Sufficient differential pressure
Latent heat of the steam
881 Btu/lb

The steam trap sizing calculator gives the condensate load of steam equipment, the trap capacity required with a safety factor, the capacity per trap when several traps share the load, and the differential pressure across the trap.

How the calculation works

  • Enter the heat load of the equipment (heat exchanger, coil, tracing line or process) and select the steam pressure at the trap inlet.
  • Enter the back pressure at the trap outlet (the condensate return line) and the number of traps that share the load.
  • Choose the safety factor from the type of duty: 2 for a steady load, 3 for a heat exchanger or a variable load, 4 for temperature-controlled equipment.
  • The calculator divides the heat by the latent heat of the steam to get the condensate load, multiplies by the safety factor and gives the capacity needed per trap and the differential pressure.

Example

A heat exchanger takes 600,000 Btu/h from steam at 100 psig, where the latent heat is 881 Btu/lb. The condensate load is 600,000 / 881 = 681.0 lb/h. With a safety factor of 3, the required trap capacity is 2,043.1 lb/h, which two traps in parallel share as 1,021.6 lb/h each. The condensate return is at 10 psig, so the differential pressure across the trap is 90 psi, well above the minimum.

Why it matters

The calculator helps plant engineers, maintenance planners, HVAC and process designers and students to size steam traps, to check the traps of an existing heat exchanger, and to avoid water logging and steam loss. It is a first step before reading the manufacturer’s capacity charts.

Good to know

Read the capacity of the chosen trap in the manufacturer’s chart at the real differential pressure. Use a higher factor for start-up loads. Install a strainer before each trap and a check valve after it when the return is lifted. Test the traps each year, since a failed trap can waste a large amount of steam.

The heat exchanger LMTD calculator gives the duty of an exchanger, the flash steam calculator gives the steam made when hot condensate is released, the heat loss calculator covers piping and the pump power calculator sizes a condensate pump.

Frequently asked questions

What is a steam trap?

A steam trap is an automatic valve that lets condensate, air and other non-condensable gases leave a steam system and keeps the live steam in. If condensate is not removed it fills the equipment, lowers the heat transfer and causes water hammer. A trap that fails open wastes steam and one that fails closed floods the equipment, so the right size and type matter.

How is the condensate load found?

Steam gives its latent heat when it condenses, so the condensate load is the heat load divided by the latent heat of the steam at the working pressure. The latent heat falls with the pressure, from about 945 Btu/lb at 15 psig to 857 Btu/lb at 150 psig. For start-up, the load is higher because the cold equipment and the piping condense much more steam.

Why is a safety factor used?

Traps are rated at a given differential pressure and for a steady load. The real load varies, the differential pressure falls when the back pressure rises, and start-up loads are much higher than the running load. A factor of 2 is used for a steady load, 3 for a heat exchanger or a variable load, and 4 or more for a temperature-controlled unit or a drain with a siphon.

What is the differential pressure and why does it matter?

It is the pressure at the trap inlet minus the pressure at its outlet, which is the pressure that pushes the condensate through the trap. The rated capacity of a trap is given at a differential pressure, and it drops when the differential is lower. Lifting the condensate or a pressurized return line raises the back pressure and reduces the capacity, so the calculator warns when the differential is small.